Fire Hydrant Flow Test Calculator

 

Use your static pressure, residual pressure, and measured flow to estimate available flow at a chosen residual pressure. Enter pressure in psi and flow in US gallons per minute (GPM).

What each value means

 

Static pressure (psi)

The pressure at your measurement point before test water is discharged. This is the starting pressure under the water system's existing operating conditions. Record it at the same pressure measurement point used for the residual reading.

 

Residual pressure (psi)

The pressure remaining at that point while the test water is flowing. Use a stabilized reading taken at the same time as the measured GPM. Residual pressure must be lower than static pressure for this calculation.

 

Measured flow (GPM)

The flow actually discharged during the test, in US gallons per minute. If multiple outlets are flowing, use the total measured discharge associated with the residual-pressure reading. Obtain this value from a suitable flow-measurement device and its correct settings; pressure alone is not a flow measurement.

 

Desired residual pressure (psi)

The pressure at which you want to estimate available flow. The calculator starts at 20 psi, a common reference for reporting hydrant flow. Confirm the required reference and minimum permitted operating pressure with the water authority or project requirements. Choosing a value here is not an instruction to lower actual system pressure.

 

Predicted / rated flow (GPM)

The estimated flow at your chosen residual pressure. This is a calculated projection, separate from measured test discharge. If the desired pressure is below the measured residual, the calculation extrapolates beyond the measured test point. The measurement arrangement determines whether the result describes the water supply or an individual hydrant; it does not guarantee flow through a particular outlet.

 

Pressure drop (psi)

Static pressure minus measured residual pressure. A test with 60 psi static and 40 psi residual has a 20 psi pressure drop. This output uses the measured residual, not your desired residual.

 

Percentage pressure drop (%)

Pressure drop divided by static pressure, multiplied by 100. In the same example, 20 divided by 60 is a 33.3% drop. A small measured drop makes the projected flow more sensitive to instrument error and changing conditions. The calculator flags drops below 10% for review.

 

How the calculation works

Predicted flow = measured GPM × [(static pressure − desired residual pressure) ÷ (static pressure − measured residual pressure)] ^ 0.54

The symbol ^ 0.54 means raise the pressure ratio to the power of 0.54.

For example, 1,000 GPM measured at 60 psi static and 40 psi residual predicts approximately 1,454 GPM at 20 psi. If the desired residual equals the measured residual, predicted flow equals the measured GPM. Results are calculated at full precision and displayed as whole GPM, with pressure and percentage drop to one decimal place.

 

Collecting readings with Brandco equipment

The Brandco Water Supply Test set combines a Pressure Sender, Remote Display, and hydrant test cap. It lets you observe pressure from the measurement hydrant while working at the flow location. Enter the recorded static and residual readings here along with the corresponding measured discharge.

The Dual Wireless Water Pressure Gauge set adds a second pressure sender for a compatible flow-device gauge connection. Verify the device data and display settings before using its calculated GPM. This web calculator accepts readings you enter manually; it does not connect to or retrieve data from your instruments.

 

Using the estimate

Use readings from the same test conditions. Water-system demand, pump operation, and water levels can change. This estimate does not certify available capacity or replace the required test procedure. The calculator rejects missing values, nonpositive static pressure or flow, negative pressures, and residual or target pressure at or above static pressure.

Read How to Perform a Fire Hydrant Flow Test and Static vs Residual Pressure, or browse all testing resources.

 

References

The 0.54-power projection and pressure definitions are described in NFPA 291 committee revision materials. Consult the applicable edition of NFPA 291 and local requirements for the actual test. The US Fire Administration's Water Supply Systems, Volume II provides further background on water-supply testing.